5 SETTINGS
In order to implement these schemes, it is not necessary to set any setting in the element. Internal functions are always
operative and provide the following logic operands:
Table 5–104: SUPERVISION LOGIC OPERANDS
ACTUAL > INPUTS/OUTPUTS > CONTACT INPUTS > BOARD X
BEING X THE CORRESPONDING BOARD IN EACH CASE
OPERAND
CONT IP_X_CC9 (Va_COIL1)
CONT IP_X_CC10 (Vb_COIL1)
CONT IP_X_CC11 (Va_COIL2)
CONT IP_X_CC12 (Vb_COIL2)
CONT IP_X_CC13 (O7_SEAL)
CONT IP_X_CC14 (O8_SEAL)
CONT IP_X_CC15 (SUP_COIL1)
CONT IP_X_CC16 (SUP_COIL2)
A continuity failure is detected in a circuit when both voltage detectors (Va and Vb) detect lack of voltage during more than
500 ms. This function is not influenced by the breaker status.
These operands can be associated to internal signals (virtual outputs), LEDs or element outputs, to issue alarm signals or
to block elements, for example for blocking the Breaker close if an anomaly is detected in the trip circuit.
Available schemes are as follows:
1.
Without supervision
2.
With current supervision (with seal-in)
3.
With simple voltage supervision
4.
With double voltage supervision
5.
With current and simple voltage supervision (with seal-in)
6.
With current and double voltage supervision (with seal-in)
7.
With current and double voltage supervision (with seal-in) and serial resistor in voltage monitors.
The following subsections describe the different types of connection to create each supervision scheme in an easy way. As
the supervision circuits are identical, only the first group connection examples will be described, being also applicable to the
second group.
In order to assure a high isolation level between groups, the digital inputs for supervision have been located in a
symmetrical basis. That is to optimize the isolation between groups that can be connected to different batteries, and
therefore requiring a greater distance between circuits.
GEK-106310AB
DESCRIPTION
Active when voltage is detected in terminals F1 - F2 (circuit 1)
Active when voltage is detected in terminals F3 - F4 (circuit 1)
Active when voltage is detected in terminals F15 - F16 (circuit 2)
Active when voltage is detected in terminals F17 - F18 (circuit 2)
Active if current is detected by sensor in output O7 (F31-F33)
Active if current is detected by sensor in output O8 (F34-F36)
Active when continuity is detected in circuit 1
Active when continuity is detected in circuit 2
F650 Digital Bay Controller