Advertisement

5.2 PRODUCT SETUP
5.2.3.1 OVERVIEW
The fault report module defines the type of fault (three-phase, phase-to-phase, phase-to-ground), and the distance to the
fault. The fault activation signal (FAULT REPORT TRIGG) is programmed at "Setpoint > Relay Configuration >
Protection Elements".
The fault report provides fault date, fault type and fault location information.
Information referred to the last ten faults is stored as fault report and available to the user through the EnerVista 650 Setup
software or the web server application. Each fault report includes the following information:
Fault date and time
Pre-fault current and voltage in primary values
Fault current and voltages in primary values
Fault type
Distance to the fault (fault location)
Line parameters
Recloser and breaker status information
As an option, the Relay offers the possibility to display a fault-warning message on the relay HMI (selectable by setting).
5.2.3.2 FAULT REPORT SETTINGS
5
Table 5–9: FAULT REPORT SETTINGS
SETPOINT > PRODUCT SETUP > FAULT REPORT
Setting Description
Function permission
Positive sequence impedance module
Positive sequence impedance angle
Zero sequence impedance module
Zero sequence impedance angle
Line length
Display fault on HMI
Snapshot Event generation
Function permission (Function): Enabling this setting allows to create a fault report when the FAULT REPORT TRIGG is
activated.
Positive sequence impedance module (Pos Seq Module):
Positive sequence impedance Angle (Pos Seq Angle):
Zero sequence impedance module (Zero Seq Module):
Zero sequence impedance Angle (Zero Seq Angle):
Line Length:
Show Fault On HMI:
Snapshot Events:
5-8
Name
Default Value
Function
DISABLED
Pos Seq Module
3.00
Pos Seq Angle
75
Zero Seq Module
9.00
Zero Seq Angle
75
Line Length
100.0
Show Fault On HMI
DISABLED
Snapshot Events
ENABLED
Value, in ohms, of the line positive sequence
impedance module.
Value, in degrees, of the line positive sequence angle.
Value, in ohms, of the line zero sequence impedance
module.
Value, in degrees, of the line zero sequence angle.
The metering element can be kilometers or miles.
This setting enables or disables the option to display
faults on the Relay HMI.
This setting enables or disables the snapshot event
generation for the fault report element.
F650 Digital Bay Controller
5 SETTINGS

5.2.3 FAULT REPORT

Step
Range
N/A
[DISABLED – ENABLED]
0.01 Ohm
[0.01 : 250.00]
1 Deg
[25 : 90]
0.01 Ohm
[0.01 : 750.00]
1 Deg
[25 : 90]
0.1
[0.0 : 2000.0]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
GEK-106310AB