Procedure To Set The Protection Function - GE F650 Instruction Manual

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

11 APPLICATION EXAMPLES
Once the relay has been connected set protection functions and outputs according to the following steps:
Open EnerVista 650 SETUP program and under:
SETPOINT  SYSTEM SETUP   GENERAL SETTINGS
Under
SETPOINT  PROTECTION ELEMENTS   PHASE CURRENT   PHASE TOC HIGH  PHASE TOC HIGH 1
Under
SETPOINT  CONTROL ELEMENTS  INPUTS/OUTPUTS  BOARD F
Under
SETPOINT  RELAY CONFIGURATION  OUTPUTS
SELECT
Contact Output Operate 00 (Board F)
Contact Output Reset 00 (Board F)
GEK-106310AB
11.1 EXAMPLE 1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE

11.1.3 PROCEDURE TO SET THE PROTECTION FUNCTION

NAME
Phase CT Ratio
Ground CT Ratio
Stv Ground CT Ratio
Phase VT Ratio
Phase VT Connection
Nominal Voltage
Nominal Frequency
Phase Rotation
Frequency Reference
Auxiliary Voltage
NAME
VALUE
Function
Enabled
Input
Phasor DFT
Pickup Level
5.0 A
Curve
IEC Curve A
TD Multiplier
0.1
Reset
Instantaneous
Voltage Restraint
Disabled
NAME
Output Logic_00_00
Output Type_00_00
NAME
C Output Oper_00_00
C Output Reset_00_00
F650 Digital Bay Controller
VALUE
1.0 (default)
1.0 (default)
1.0 (default)
1.0 (default)
Wye
100.0 (default)
50
ABC
VI (default)
VX (default)
VALUE
Positive
Latch
SOURCE
PRESS FOR LOGIC
Phase TOC A Op
Phase TOC B Op
Phase TOC C Op
Operation bit 000
11
OR
11-3