9 BOOTCODE AND FIRMWARE UPGRADE
11. It is important to switch the Relay OFF and ON again during the time shown by the progress bar; in case this time
expires, the program will offer the option to continue with the process or to postpone, verify the correct RS232
connections and try again later. Notice that the serial COM PORT used in the boot upgrade procedure is the one
selected in step 4 above.
12. If the relay gets stuck during the upgrading process after switching OFF and ON the relay, giving error message
shown, it is due to no serial communication via the front RS232 port. Please check serial cable and serial settings
connection. At this point the relay will not be upgraded.
After switching it OFF and ON it will continue working with the former firmware and bootware versions.
13. After switching the relay OFF and ON, if the serial communication between EnerVista 650 Setup and the relay is
correct the program shows the following message (Figure 9–14:):
Then it requires the confirmation to proceed to upgrade:
GEK-106310AB
Figure 9–15: LOADING UPDATE FILE ERROR MESSAGE
Figure 9–16: CONFIGURATION PROCESS IN PROGRESS
F650 Digital Bay Controller
9.2 BOOTWARE UPGRADE