GE F650 Instruction Manual page 190

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

5 SETTINGS
5.4.2.5
I2T CURVES
The following formulas define this type of curves:
where:
t = Operation time in seconds
Dial = multiplier setting
I = Input current
Itap = Current pickup value
T
= reset time in seconds
RESET
Table 5–38: TRIPPING TIME IN SECONDS FOR I2T CURVES
DIAL
CURRENT (I/ITAP)
1.5
2.0
0.01
0.444
0.250
0.10
4.444
2.500
1.00
44.444
25.000
10.00
444.444
250.000
100.00
4444.444
2500.000
600.00
26666.667 15000.000 6666.667
5.4.2.6 DEFINITE TIME CURVES
The definite time makes the element trip when the current value is maintained beyond the pickup value during a longer time
period than the set value. The Dial setting allows modifying this time frame from instantaneous to 900 seconds in steps of
10 ms.
5.4.2.7 RECTIFIER TIME CURVES
Rectifier curves are generated from the following formulas:
where:
T = Operation time (in seconds).
TDM = Multiplying factor
I = Input current
I
= Pickup current
pickup
T
= Reset time (in seconds) assuming a 100% of power capacity and that the reset is activated
reset
GEK-106310AB
3.0
4.0
5.0
0.111
0.063
0.040
1.111
0.625
0.400
11.111
6.250
4.000
111.111
62.500
40.000
1111.111
625.000
400.000
3750.000
2400.000
F650 Digital Bay Controller
5.4 PROTECTION ELEMENTS
6.0
7.0
8.0
0.028
0.020
0.016
0.278
0.204
0.156
2.778
2.041
1.563
27.778
20.408
15.625
277.778
204.082
156.250
1666.667
1224.490
937.500
9.0
10.0
5
0.012
0.010
0.123
0.100
1.235
1.000
12.346
10.000
123.457
100.000
740.741
600.000
5-43

Advertisement

Table of Contents
loading

Table of Contents