10.8 VERIFICATION OF MEASUREMENT

10.8VERIFICATION OF MEASUREMENT
Set the relay as follows
GENERAL SETTINGS
NAME
PHASE CT RATIO
GROUND CT RATIO
STV GROUND CT RATIO
PHASE VT RATIO
PHASE VT CONNECTION
NOMINAL VOLTAGE
NOMINAL FREQUENCY
PHASE ROTATION
FREQUENCY REFERENCE
AUXILIARY VOLTAGE
NOTE:
ALL ANGLES INDICATED ARE LAGGING ANGLES
ALL VALUES OBTAINED IN THIS TEST MUST BE THE ONES CORRESPONDING TO THE PHASOR ONES
Apply the following voltage and frequency values to the relay:
Verify that the relay measures the values with an error of ±1 % of the applied value from 10V to 208V.
Apply the following current and frequency values to the relay:
Verify that the relay measures the values with an error lower than ±0.5% of the test value or ± 10 mA, whichever is greater,
for phases and ground.
Verify that the relay measures the values with an error lower than ±1.5% of the test value or ± 1 mA, whichever is greater,
for sensitive ground (SG).
10
10-8
VALUE
1.0
1.0
1.0
1.0
WYE
100 V
50 Hz
ABC
VI
VX
CHANNEL
ANGLE
FREQUENCY
50 Hz
VI
0
VII
120º
0
VIII
240º
0
VX
0
CHANNEL
ANGLE
FREQUENCY
50 Hz
Ia (A)
45º
0
Ib (A)
165º
0
Ic (A)
285º
0
IG (A)
0
ISG (A)
0
F650 Digital Bay Controller
UNITS
RANGE
0.1
1.0-6000.0
0.1
1.0-6000.0
0.1
1.0-6000.0
0.1
1.0-6000.0
N/A
WYE – DELTA
0.1
1-2250 V
1 Hz
50-60 Hz
N/A
ABC – ACB
N/A
VI-VII-VIII
N/A
VX – VN
60 Hz
50 Hz
60 Hz
50 Hz
5
50
100
150
5
50
100
150
5
50
100
150
5
50
100
150
60 Hz
50 Hz
60 Hz
50 Hz
15
10
5
1
15
10
5
1
15
10
5
1
15
10
5
1
5
1
0.1
0.01
10 COMMISSIONING

10.8.1 VOLTAGES

60 Hz
200
200
200
200

10.8.2 PHASE CURRENTS

60 Hz
0.1
0.1
0.1
0.1
0.005
GEK-106310AB