6 ACTUAL VALUES
SYNCHK CLOSE PERM:
Synchrocheck COND OP:
SLIP CONDITION:
BUS FREQ > LINE FREQ:
BUS FREQ < LINE FREQ:
VOLTAGE DIFFERENCE:
FREQ. DIFFERENCE:
GEK-106310AB
General Closing permission of the Synchronism unit. It contemplates all possible
situations, live line-live bus conditions, and the closing permission logics (dead line-
dead bus, live line- dead bus, dead line-live bus). Note: in case the Function is
disabled, the Closing permission signal will be activated in order not to interfere with
possible logics where it is included. If the synchronism unit is enabled, this signal will
only be activated in the closing conditions established by setting.
Closing permission according to permission logics (DL-DB, LL-DB, DL-LB).
DL-DB OPERATION: Closing permission in dead line – dead bus condition.
DL-LB OPERATION: Closing permission in dead line – live bus condition.
LL-DB OPERATION: Closing permission in live line – dead bus condition.
Internal signal indicating frequency slip between the line voltage and bus voltage
phasors.
Busbar Frequency higher than line frequency
Busbar Frequency lower than line frequency
Voltage difference between the line and the busbar in volts (secondary values), only
available if the Synchrocheck element is enabled.
Frequency difference between the line and the busbar in Hz, only available if the
Synchrocheck element is enabled.
F650 Digital Bay Controller
6.2 STATUS
6
6-11