APPENDIX C
c) IMPLEMENTATION TABLE (SHEET 3 OUT OF 3)
OBJECT
Object
Variation
Description
No.
No.
32-Bit Analog Input Reporting
34
2
Deadband
See Note 1
50
0
Time and Date - All Variations
Time and Date
50
1
See Note 1
52
2
Time Delay Fine
60
0
Class 0, 1, 2, and 3 Data
60
1
Class 0 Data
60
2
Class 1 Data
60
3
Class 2 Data
60
4
Class 3 Data
80
1
Internal Indications
No Object (function code only)
See Note 3
No Object (function code only)
No Object (function code only)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28,
respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01
(for change-event objects, qualifiers 17 or 28 are always responded).
Note 3: Cold restarts are implemented the same as warm restarts – The F650 is not restarted, but the DNP process is restarted.
GEK-106310AB
REQUEST
Function Codes
Qualifier Codes
(dec)
(hex)
00,01
2
(write)
07,08
17,28
00,01
06
(no range, or all)
1
(read)
07,08
17,28
00,01
06
(no range, or all)
1
(read)
07
(limited qty=1)
2
(write)
08
(limited qty)
17,28
1
(read)
2
(write)
1
(read)
20
(enable unsol)
06
(no range, or all)
21
(disable unsol)
22
(assign class)
06
(no range, or all)
1
(read)
20
(enable unsol)
06
(no range, or all)
21
(disable unsol)
07,08
22
(assign class)
1
(read)
20
(enable unsol)
06
(no range, or all)
21
(disable unsol)
07,08
22
(assign class)
1
(read)
20
(enable unsol)
06
(no range, or all)
21
(disable unsol)
07,08
22
(assign class)
00
(start-stop)
2
(write)
(index must =7)
13
(cold restart)
14
(warm restart)
23
(delay meas.)
F650 Digital Bay Controller
C.3 IMPLEMENTATION TABLE
RESPONSE
Function Codes
(start-stop)
(limited qty)
(index)
(start-stop)
129
(response)
(limited qty)
(index)
(start-stop)
129
(response)
(index)
129
(response)
(limited qty)
(limited qty)
(limited qty)
Qualifier Codes
(hex)
00,01
(start-
stop)
17,28
(index)
See Note 2
00,01
(start-
stop)
17,28
(index)
C
See Note 2
07
(limited qty)
quantity=1
C-9