11 APPLICATION EXAMPLES
11.2 EXAMPLE 2: TOC PROTECTION + RECLOSING SETTINGS PROCEDURE
The purpose of this exercise is to introduce the F650 User about the way to set a protection scheme including:
Trip operation of a phase time overcurrent protection.
Two reclosing shots with successful fault clearing.
Synchronism check action to verify two ends voltage conditions previous to perform each reclosing action.
This procedure is described in Example Nº 1. Therefore check the actual PC communication status to assure a fast and
reliable communication with F650 relay.
This procedure is fully described in paragraph 13.3 (see Example Nº 1). Therefore it is not necessary to explain it here
again except about the small modifications required for the actual exercise, as well the additional settings not used until
now (i.e. recloser and synchrocheck).
Therefore, by having the F650 set like in the previous exercise (paragraph 13), the new settings and changes to be done in
the relay to work in a protection-reclosing scheme are:
Under
SETPOINT SYSTEM SETUP BREAKER BREAKER SETTINGS
Under
SETPOINT INPUTS/OUTPUTS CONTACT I/O BOARD F
Under
SETPOINT RELAY CONFIGURATION PROTECTION ELEMENTS
GEK-106310AB
11.2 EXAMPLE 2: TOC PROTECTION + RECLOSING SETTINGS PROCEDURE
11.2.3 PROCEDURE TO SET THE PROTECTION FUNCTION
NAME
Number of Switchgear
NAME
Output Logic_00_00
Voltage Threshold B_00
Debounce Time B_00
Input Type_00_00 (CC1)
Delay Input Time_00_00 (CC1)
Output Type_00_00
Pulse Output Time_00_00
SELECT
SOURCE
AR Initiate
PRESS FOR LOGIC
Phase TOC A Op
Phase TOC B Op
Phase TOC C Op
AR Conds Input
Synch Close Perm
F650 Digital Bay Controller
11.2.1 DESCRIPTION OF THE EXERCISE
11.2.2 PROCEDURE TO COMMUNICATE THE RELAY
VALUE
1
VALUE
Positive
80V
10 ms
Positive
0 ms
Normal
500 ms
OR
11
11-5