9.2 COMMUNICATION PARAMETERS
9.2 COMMUNICATION PARAMETERS
Before proceeding with the upgrade process, it is mandatory to check the following:
1.
Since F650 Setup Program acts as a TFTP sever, any other TFTP server installed in the PC must be disabled.
Check if any other TFTP server is installed in the PC and/or if any other device is using Port 69 that it might be
installed by default during the PC startup. To disable it please proceed as follows in the PC:
At STARTUP>MY PC>Right Mouse key>MANAGE>SERVICES & APPLICATIONS> SERVICES
Select the operative TFTP server
Right Mouse key>MANUAL or STOP
Reboot PC (if MANUAL)
2.
Ethernet Connection/Type - Both boot code and firmware upgrade processes require Ethernet communications. It is
strongly recommended to use a direct connection between the PC and the relay using a Cross-Over RJ45 Ethernet
cable, instead a direct connection through a hub or switch. In no one case upgrading will be done using a Local Area
Network (LAN).
Serial RS232 Communication - Serial communication is necessary only to perform the bootware upgrade.
3.
Relay IP Address - It must be assigned a IP address to the relay in the Ethernet parameters via HMI at PRODUCT
SETUP>COMMUNICATION>ETHERNET>ETHERNET1 menu or via Enervista 650 Setup at SETPOINT>PRODUCT
SETUP>COMMUNICATION SETTINGS>NETWORK (Ethernet) 1 as shown in the Table 9–1:
Table 9–1: ETHERNET PARAMETERS
PRODUCT SETUP>COMMUNICATION SETTINGS >NETWORK (ETHERNET) 1
NAME
IP Address Oct1
IP Address Oct2
IP Address Oct3
IP Address Oct4
Netmask Oct1
Netmask Oct2
Netmask Oct3
Netmask Oct4
Gateway IP Oct1
Gateway IP Oct2
Gateway IP Oct3
Gateway IP Oct4
4.
PC IP Address - In the case the relay has been boot code previously upgraded (section 9.2), the IP address and other
parameters already assigned in the process will be:
9
IP Address:192.168.37.177
Netmask:255.255.255.0
Gateway:192.168.37.10
9-2
9 BOOTCODE AND FIRMWARE UPGRADE
VALUE
UNITS
192
168
37
177
255
255
255
0
192
168
37
10
F650 Digital Bay Controller
RANGE
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
GEK-106310AB