2.4 TECHNICAL SPECIFICATIONS
2.4.5.7 WAR-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
Range:
Parameters:
Update rate:
2
2.4.5.8 FREQUENCY
Accuracy:
2.4.5.9 ANGLE
Accuracy:
2.4.6.1 AC CURRENT INPUTS
CT Ratio:
Rated currents:
Relay Burden:
Current Withstand
2-24
±2.0% of the reading
-2147483 to +2147483 MVArh
3-phase only
100 ms
+/- 0.03Hz From 30 to 80 Hz
±3º
1.0 to 6000.0 in steps of 0.1
Appropriate for 1 or 5 A. F650 has universal range for CT (valid for 1 or 5 A to
only one terminal).
< 0.04 Ohm
Continuous at 20 A
1 second at 500 A for phases and ground
1 second at 50 A for sensitive ground
F650 Digital Bay Controller
2 PRODUCT DESCRIPTION
2.4.6 INPUTS