7 IEC 61850 PROTOCOL
2.5 Logical Nodes for generic references. LN Group: G
2.5.1 GGIO (Generic process I/O)
2.5.1.1 GGIO
This logical node class is used is used to map digital and analogue inputs of I/O boards F, G, H and J.
GGIO class
Attribute
Attribute
Name
Type
GGIO
Data
Common Logical Node Information
Mod
INC
Beh
INS
Health
INS
NamPlt
LPL
Status information
BoardSt
SPS
Ind1
SPS
Ind2
SPS
Ind32
SPS
Ind33
SPS
..
..
Ind48
SPS
Measured Values
AnIn1
MV
AnIn2
MV
AnIn8
MV
GEK-106310AB
Explanation
Generic process I/O
Mode
Behaviour
Health
Name plate
Board Status
General Indication ( binary input )
General Indication ( binary input )
General Indication ( binary input )
General Indication ( binary input )
..
General Indication ( binary input )
Analogue input
Analogue input
Analogue input
F650 Digital Bay Controller
7.2 IEC 61850 PROFILE FOR F650
M/O/E
Notes
M
Status-only
M
M
M
E
Board Status.
True:
board present and working correctly
False:
board not present
board present and board model
mismatch
board present and hardware failure
O
Contact Input 1
O
Contact Input 2
O
Contact Input 32
O
Contact Output 1
..
..
O
Contact Output 16
O
Analog Input 1
O
Analog Input 2
O
Analog Input 8
7