GE F650 Instruction Manual page 398

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

7 IEC 61850 PROTOCOL
2.2.2.3 gndPTOC
This logical node class is used for ground time overcurrent and sensitive ground time overcurrent. There are 6 instances
inside of this logical node inside the device.
PTOC class
Attribute
Attribute
Name
Type
PTOC
Data
Common Logical Node Information
Mod
INC
Beh
INS
Health
INS
NamPlt
LPL
Status Information
Str
ACD
Op
ACT
Blk
ACT
Settings
TmACrv
CURVE
StrVal
ASG
TmMult
ASG
RsMod
ING
InMagTyp
ING
PTOCEna
SPG
Note: ACT includes origin attribute in ST, this is implemented according to Tissue 68.
2.2.3 PTOF (OverFrequency)
This logical node class is used for overfrequency and has 6 instances inside the device.
PTOF class
Attribute
Attribute
Name
Type
PTOF
Data
Common Logical Node Information
Mod
INC
Beh
INS
Health
INS
NamPlt
LPL
Status Information
Str
ACD
Op
ACD
Blk
ACT
Settings
StrVal
ASG
BlkVal
ASG
OpDlTmms
ING
RsDlTmms
ING
PTOFEna
SPG
Note: ACT includes origin attribute in ST, this is implemented according to Tissue 68.
GEK-106310AB
Explanation
Time overcurrent
Mode
Behaviour
Health
Name plate
Start
Operate
Block
Operating curve type
Start value
Time dial multiplier
Reset Mode
Input Type
Function TOC enable
Explanation
OverFrequency
Mode
Behaviour
Health
Name plate
Start
Operate
Block
Start value (frequency)
Voltage Block Value
Operate Delay Time
Reset Delay Time
Function TOF enable
F650 Digital Bay Controller
7.2 IEC 61850 PROFILE FOR F650
M/O/E
Notes
M
Status-only
M
M
M
M
TOC PKP
M
TOC OP
E
TOC BLK
M
Curve
O
Pickup Level (0,05 – 160)
O
TD Multiplier (0 – 900)
E
Reset (instantaneous, lineal)
E
Input (Phasor, RMS)
E
Function
M/O/E
Notes
M
Status-only
M
M
M
M
TOF PKP
M
TOF OP
E
TOF BLK
O
Pickup Level (20-65)
O
Minimun Voltage (10-300)
O
Trip Delay (0-900000)
Units in miliseconds
O
Reset Delay (0-900000)
Units in miliseconds
E
Function (Enable,Disable)
7
7-29

Advertisement

Table of Contents
loading

Table of Contents