GE F650 Instruction Manual page 785

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

H.1 FACTORY DEFAULT SETTINGS
SETPOINT > CONTROL ELEMENTS >POWER
WATT GND FLT HIGH 1> WATT GND FLT HIGH 2 > WATT GND FLT HIGH 3
WATT GND FLT LOW 1> WATT GND FLT LOW 2 > WATT GND FLT LOW 3
SETTING DESCRIPTION
Function permission
Supervision minimum voltage
Source of operating current.
Pickup Level for Overcurrent
Pickup Delay for Overcurrent
Pickup Level for operating Power
Max torque angle
Pickup Delay for Operating Power
Curve shape
Multiplier
Snapshot event generation
H
H-18
NAME
DEFAULT VALUE
Function
DISABLED
Voltage Pickup Level
2
Current selection
IN
OC Pickup Level
0,005
OC Pickup Delay
0,2
Power Pickup
0,01
MTA
0
Power Pickup Delay
0,2
Curve
DEFINITE TIME
Multiplier
1
Snapshot Event
DISABLED
F650 Digital Bay Controller
STEP
RANGE
N/A
[DISABLED-ENABLED]
0.01 V
[2.00 : 70.00]
N/A
[IN-IG]
0.001A
[0.005 : 0.400]
0.01 s
[0.00 : 600.00]
0.01 W
[0.01 : 4.50]
1 Deg
[0 : 360]
0.01 s
[0.00 : 600.00]
N/A
[DEFINITE TIME -
INVERSE TIME - USER
CURVE A - USER CURVE
B - USER CURVE C -
USER CURVE D]
0.01 s
[0.02 : 2.00]
N/A
[DISABLED-ENABLED]
APPENDIX H
USER
VALUE
GEK-106310AB

Advertisement

Table of Contents
loading

Table of Contents