5.3 SYSTEM SETUP
Table 5–21: FLEX CURVE SETTINGS
SETPOINT > SYSTEM SETUP > FLEX CURVES
FLEX CURVES A > FLEX CURVES B> FLEX CURVES C > FLEX CURVES D
Setting Description
Values for reset points 0.00 pkp
Values for reset points 0.05 pkp
...
Values for reset points 0.97 pkp
Values for reset points 0.98 pkp
Values for operation points 1.03 pkp
Values for operation points 1.05 pkp
...
Values for operation points 19.50 pkp
Values for operation points 20.00 pkp
The definition of the curve points can be introduced directly in the Flex Curve settings menu. Alternatively they can be
created using the graphical tool provided by pressing "Edit Curve" in the Flex curves menu in EnerVista 650 Setup.
In the user curve edit screen (see Figure 5–3:), a base curve can be selected, from the Standard Curves menu. This curve
will be used as a template to create the user curve. Once the standard curve is viewed, it is possible to make the user curve
(operate, reset or both) reconcile the standard curve, using the Flex curve > set flex curve from the standard curve, and
then modifying any of the points by editing in the table the corresponding value.
The user can also view a different curve model to the one the FlexCurve has been adapted to, and compare both models to
5
adopt the most appropriate values in each case. If once the user curve has been configured, the user wants to store the
information, the "Flex Curve > Exit with Data" menu must be selected. If the results are not to be saved, the Exit without
Data option must be selected. Now, calculated points must be saved in the Flex Curve using the "Store" option.
5-26
Name
Time 0.00xPKP [RST]
Time 0.05xPKP [RST]
...
Time 0.97xPKP [RST]
Time 0.98xPKP [RST]
Time 1.03xPKP [OP]
Time 1.05xPKP [OP]
...
Time 19.50xPKP [OP]
Time 20.00xPKP [OP]
Figure 5–3: FLEXCURVES EDITION
F650 Digital Bay Controller
Default Value
Step
Range
0.000
0.001 s
[0.000 : 65.535]
0.000
0.001 s
[0.000 : 65.535]
...
...
...
0.000
0.001 s
[0.000 : 65.535]
0.000
0.001 s
[0.000 : 65.535]
0.000
0.001 s
[0.000 : 65.535]
0.000
0.001 s
[0.000 : 65.535]
...
...
...
0.000
0.001 s
[0.000 : 65.535]
0.000
0.001 s
[0.000 : 65.535]