4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
4.1.8.5 INPUT/OUTPUTS
Section that contains the settings for all input and output boards and the Force Outputs and Virtual inputs activation tools.
Table 4.12: GENERAL OVERVIEW OF "INPUTS/OUTPUTS" SETTINGS MENU.
INPUTS/
OUTPUTS
4
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
This section shows the settings related to inputs and outputs for the different boards available in F650 (F, G, H, J).
Table 4.13: GENERAL OVERVIEW OF "INPUTS/OUTPUTS>CONTACT I/O" SETTINGS MENU.
CONTACT I/O
4.1.8.6 RELAY CONFIGURATION
This is the relay configuration section in which the relay can be configured using internal states or already compiled
equation on PLC Editor.
Table 4.14: GENERAL OVERVIEW OF RELAY CONFIGURATION MENU:
RELAY CONFIG
4-20
Frequency rate of
Frequency rate of change function (81R).Grouped element.
change
Load Encroachment
Load Encroachment function. Grouped element.
Inputs and outputs settings for all boards in F650. The I/O settings
Contact I/O
configuration can only be performed through EnerVista 650 Setup, not
HMI available.
This menu allows activating each contact output in the relay, to facilitate
Force Outputs (*)
maintenance testing. On line mode only.
This menu allows operating virtual inputs. These variables are used as
inputs to logic schemes configured in the relay. Virtual inputs can be
Virtual Inputs (*)
operated in a latched mode (32 latched virtual inputs) or in Self-reset
mode (32 self reset virtual inputs).
This menu allows configuring remote inputs coming from other devices
Remote Comms.
through GSSE messages. Available for IEC61850 (6) models only.
Board F
Board located in first slot, always connected.
Board located in second slot, depends on model definition. If model is
Board G
type G0 there is no board in second slot.
Board H
Board located in first slot of CIO Module (external inputs/outputs module)
Board located in second slot of CIO Module (external inputs/outputs
Board J
module)
Outputs
Configuration of contact output operate and reset signals for all boards.
15 LEDs fully configurable from any logical variable, contact or virtual
input. First 5 LEDs are latched by hardware, the rest are self-reset but
LEDs
can be latched through PLC configuration. From the LED configuration
screen, it is possible to print the vertical LED label for the relay.
Configurable operations up to 24. Operation texts, interlocks, final states,
Operations
frontal keys, time outs and masters.
This tab allows assigning operands (logic signals) as inputs to different
Protection Elements
protection elements. To block, reset, initiate the different protection
elements inputs.
Trigger and up to 16 digital channels to be included in oscillography
records, are programmable from any logical variable, contact or virtual
input. Text configuration is only for off-line mode.
Oscillography
NOTE: This screen is used for the configuration of digital channels and
oscillography trigger. The rest of parameters, such as function enabling/
disabling, sampling rate, number of oscillography files, etc. must be set
on the Setpoint>Product Setup>Oscillography menu.
F650 Digital Bay Controller
GEK-106310AB