7 IEC 61850 PROTOCOL
7.3 IEC 61850 CONFIGURATOR
a) OPEN IEC61850 FILE FROM DISK
The "Open IEC 61850 file from disk" menu allows the user to work in off line mode to configure IEC 61850 protocol in 650
devices. The tool works with files of *.iec extension which contain the icd file from the devices and proprietary files needed
for the whole configuration.
In the EnerVista 650 Setup default files you will find the "F650_Vxxx.iec" corresponding to the firmware version related to
the EnerVista instalation.
After opening the file all the ICD data will be displayed in the ICD/CID tab and the user can start configuring the IEC 61850
protocol in 650 devices.
b) SAVE IEC 61850 FILE TO DISK
After modifying the files using this tool the user can save them in the computer under the *.iec format, using the "Save IEC
61850 file to disk" option.
c) RECEIVE IEC 61850 FILE FROM DEVICE
The user can select the option "Receive IEC 61850 file from device" to retrieve the IEC 61850 files from the 650 device for
visualization or further modifications.
If the user is already communicating with the 650 device using the "Modbus/TCP" option in the "Communication" menu the
retrieving files options will be performed over the IP Address selected on the Communication menu.
If the user is not communicating with a relay when the "Receive IEC 61850 file from device" menu is selected, the program
will pop up a menu asking to introduce the IP Address for the unit.
After retrieving the files, all the ICD data will be displayed in the ICD/CID tab and the user can start configuring the IEC
61850 protocol.
d) SEND IEC 61850 FILE TO DEVICE
The user can send the IEC 61850 files to the 650 relays using the "Send IEC 61850 file to device" menu, this menu can be
user either in off line or on line mode.
If the user is already communicating with the 650 device using the "Modbus/TCP" option in the "Communication" menu the
sending files options will be performed over the IP Address selected on the Communication menu.
If the user is working in off line mode using the "Open IEC 61850 file from disk" option, when the "Send IEC 61850 file to
device" option is selected, the program will pop up a window to introduce the IP Address.
This pop up menu will also appear if the user selects the "Send IEC 61850 file to device" option after retrieving the files
using the "Receive IEC 61850 file from device".
7
e) EXPORT *. ICD
The F650.icd file can be exported from the F650.iec files using the "Export *. Icd" option provided in the IEC 61850
configurator tool. This icd file can be used for goose configuration in other devices.
f) EXIT
When the user selects to exit the program, the program will ask the user to save to disk or send the configuration to the
relay before leaving the application, if desired.
Figure 7–6: EXIT IEC 61850 CONFIGURATOR?