APPENDIX A LOGIC OPERANDSA.1LOGIC OPERANDS
OPERANDS - F650 - MODEL FX - GX
INTERNAL SYSTEM STATUS
AUTOCHECK INTERNAL STATES (CRITICAL)
DSP Internal States (Critical to metering and
protection)
Flash Internal States (Critical to Relay configuration
and stored data)
IO Board States (Critical to operation and
protection)
IEC61850 INTERNAL STATES (NON CRITICAL)
IEC61850 Internal States
OTHER INTERNAL STATES (NON CRITICAL)
GEK-106310AB
DSP Communication Error: (0) Rignt communications
DSP COMM ERROR
between DSP and main processor; (1) Communication
Error between DSP and main processor
Magnetic Module Error: (0) Right Communication
MAGNETIC MODULE
between DSP and magnetic module processor; (1)
ERROR
Communication Error between DSP and magnetic
module processor
Calibration Error: (0) Right calibration values stored; (1)
CALIBRATION ERROR
The calibration values stored are out of the calibration
limits.
E2prom status :(0) Not configured or problems during
E2PROM STATUS
writing process ; (1) Configured and OK
Board F status: (0) Inactive - There is no communication
BOARD F STATUS
with the board (1) Active - There is communication with
the board.
Board G status: (0) Inactive - There is no communication
BOARD G STATUS
with the board (1) Active - There is communication with
the board.
Board H status: (0) Inactive - There is no communication
BOARD H STATUS
with the board (1) Active - There is communication with
the board.
Board J status: (0) Inactive - There is no communication
BOARD J STATUS
with the board (1) Active - There is communication with
the board.
UNKNOWN: when the relay has not the IEC61850 proto-
col in the relay model the ICD status is unknow to the
unit
ICD ERROR: There is an error in the ICD file and the
relay ICD is not operative. To solve this issue it is neces-
sary to send a correct ICD to the relay using the
IEC61850 configurator tool. When the ICD error is raised
the IEC 61850 will not be operative (the IEC 61850 cli-
ent, reports and gooses will not work). It is advisable to
include the ICD ERROR in the main error signal config-
ured by the customers in their applications.
ICD STATUS
MODIFIED: The settings have been changed in the icd
but they are still not wrtten in the icd file in the relay
IN PROGRESS: The icd setting are being written to the
file in the relay
OK WITHOUT DAIS: The relay has not got the "Use DOI
&DAI" setting enabled (true) and it is working properly
with the ICD file.
OK: The relay has got the "Use DOI &DAI" setting
enabled (true) and it is working properly with the ICD file.
When that setting is set to true the icd setting will prevail
over the relay settings.