13.6 What Should I Do If the ESU Cable Connection
Detection Abnormal Alarm Is Generated on the
WebUI?
Step 1 Press the reset button (
restarts cable connection detection.
----End
13.7 How Do I Perform a Dielectric Voltage Withstand
Test on the AC Side of an ESS?
Prerequisites
1.
2.
3.
4.
Figure 13-4 3U subrack positions
Issue 15 (2023-11-01)
NO TE
If the alarm persists, contact your dealer or technical support.
Turn on the main switch of the AC circuit breaker, as shown by ① in the
figure. Turn off other switches.
NO TE
Make sure the power switch of the 3 U or 2 U subrack is off, as shown by ② in the
figure.
Remove the SMU from the 3 U or 2 U subrack, as shown by ③ in the figure.
Disconnect the power meter fuse, as shown by ④ in the figure.
Disconnect the main neutral wire, as shown by ⑤ in the figure.