ECC800 Data Center Controller
User Manual
Step 2 Add a PMAC615.
1.
2.
Table 8-9 Adding a PMAC615
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
3.
----End

8.1.8.9 How to Set and Add a PMAC625 AC Meter?

Prerequisites
One end of the straight-through cable has been connected to the RS485 port on the PMAC625
AC meter, and the other end has been connected to the COM port on the ECC800.
Context
Issue 05 (2019-09-16)
Log in to the ECC800 WebUI as an administrator.
Add a PMAC615.
Parameter
Name
Device attribute
Device Type
Connect To
Communications
Port
Device Address
Click Test Connect to check whether the PMAC615 connects to the ECC800 properly.
If the PMAC615 connects to the ECC800 properly, click Confirm. The connected
devices are displayed in the Number of connected devices list.
If the PMAC615 does not connect to the ECC800 properly, check whether the cable
between the PMAC615 and the ECC800 is connected properly, whether the
PMAC615 and ECC800 are running properly, and whether the input parameters are
consistent with the PMAC615 parameters.
The model of the three-phase AC power meter for the PDC is PMAC625.
When connecting devices, you are advised to add devices one by one. If all devices have
been added and powered on, only the BLINK function of the ETH converter can be used
to identify the mapping between the PMAC625 and ETH converter.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Electricity Meter from the drop-down list
box.
Select PMAC615 from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the PMAC615 is
connected to the COM3 port on the ECC800. If the
PMAC615 is connected to another port, enter the number
of the connected port.
In this example, Device Address is set to 8. During
actual configuration, set the device address for the
PMAC615 based on the actual situation.
8 FAQ