How To Set And Add A Ups2000-G - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Procedure
Step 1 Start the integrated UPS, and tap System Info on the LCD.
Step 2 Choose System Info > Settings, enter the user name admin and password 000001, and then
tap
Step 3 Choose Settings > Communication, and set IP address assign to Automatic(DHCP).
Step 4 Tap
----End

8.1.8.2 How to Set and Add a UPS2000-G?

Prerequisites
One end of the straight-through cable has been connected to the COM_1 or COM_2 port on
the Modbus expansion card of the UPS2000-G, and the other end has been connected to the
COM port on the ETH converter.
Procedure
Step 1 Set monitoring parameters for the UPS2000-G.
Table 8-1 Setting a device address
Device
Addre
ss
1
2
3
4
Issue 05 (2019-09-16)
. In the displayed dialog box for confirming the password, tap OK.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
to go back to the main menu screen.
After setting parameters for the integrated UPS, the ECC800 discovers the access from the integrated
UPS automatically.
Set monitoring parameters for the UPS2000-G-(1 kVA-3 kVA).
Operate the DIP switch SW1 on the optional Modbus card to set the UPS2000-G device address. Toggle
switches 1 to 8 of DIP switch SW1 specify the device address in binary mode. ON indicates 1, and OFF
indicates 0.
Toggle
Toggle
Switch
Switch
1
2
ON
OFF
OFF
ON
ON
ON
OFF
OFF
Set monitoring parameters for the UPS2000-G-(6 kVA–20 kVA).
Copyright © Huawei Technologies Co., Ltd.
Toggle
Toggle
Toggle
Switch
Switch
Switch
3
4
5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
Toggle
Toggle
Toggle
Switch
Switch
Switch
6
7
8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
8 FAQ
183