Access Control System; Aisle Or Room Access Control System - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Indicators
Table 3-17 Indicators on a smart ETH gateway
Indicator
PWR
RUN
ALM

3.2.3 Access Control System

The access control system applies to the equipment room, aisle containment, and cabinet
doors.

3.2.3.1 Aisle or Room Access Control System

The access control system collects and monitors data about the access of devices and
personnel to ensure access security.
Diverse access control devices such as the fingerprint and card reader with a keypad,
fingerprint and card reader, and card reader with a keypad are supported. Note that the
communication distance between an access control device and an access actuator should be
less than or equal to 5 meters.
Issue 05 (2019-09-16)
Color
Name
Green
Power input
status indicator
Green
Module
running status
indicator
Red
Alarm
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power supply is
abnormal.
Blinking at
The smart ETH gateway
long
successfully registers with
intervals
the ECC800 and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at
The smart ETH gateway does
short
not register with the ECC800
intervals
(the indicator blinks at 4 Hz,
on for 0.125s and then off for
0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.
Steady on
A system failure alarm is
generated.
Off
No system alarm is
generated.
3 Device Description