ECC800 Data Center Controller
User Manual
Item
5
6
7
----End
6.8.5 Setting the Temperature Map
If the temperature map function is configured, follow the instructions provided in this section
to commission it.
Prerequisites
1.
(1) ECC800
Issue 05 (2019-09-16)
Specifications
Air inlet temperature of the smart cooling product
Refrigerant status
Air outlet temperature of the smart cooling product
Cables to the NTC and T/H sensors have been connected.
Figure 6-47 Wiring diagram for the temperature map function
Sensors NTC1 to NTC6 are installed in the following positions of the cabinet respectively: upper
part of the front door, middle part of the front door, lower part of the front door, upper part of the
rear door, middle part of the rear door, and lower part of the rear door.
A maximum of eight T/H sensors can be cascaded to each COM port.
Copyright © Huawei Technologies Co., Ltd.
(2) T/H sensor
6 Feature Description
(3) NTC
154