8.1.8.37 How to Set and Add the T/H Sensor (BOM Number: 02311FQG)?

Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port on the T/H
sensor, and the other end has been connected to the COM port on the ECC800.
Procedure
Step 1 Set the T/H sensor device address.
Set the T/H sensor device address through the DIP switch on the T/H sensor.
Toggle switches 1–6 are used to set device addresses, toggle switch 7 is reserved, and toggle
switch 8 is used to switch the temperature unit.
Device addresses are set in binary coding format in the range of 1–63. The first bit is the least
significant bit, and the sixth bit is the most significant bit. ON indicates 1 and OFF indicates
0.
Figure 8-20 T/H sensor Dip switch
Step 2 Add a T/H sensor.
1.
2.
Table 8-36 Adding a T/H sensor
Path
Issue 05 (2019-09-16)
Log in to the ECC800 WebUI as an administrator.
Add a T/H sensor.
Parameter
Name
Copyright © Huawei Technologies Co., Ltd.
Setting