2.
Step 3 On the Controls tab page, set the smart cooling product control parameters (such as on/off
control parameters).
After the smart cooling product is shut down, the temperature of the smart module increases
and data running is affected. Exercise caution when performing this operation.
----End

8.1.8.22 How Do I Add and Set an AIRSYS Air Conditioner?

Procedure
Step 1 Add an AIRSYS air conditioner.
1.
2.
Table 8-16 Adding an AIRSYS air conditioner
Path
Choose System
Settings >
Device
Management,
and click Add
Device.
Issue 05 (2019-09-16)
Choose Monitoring > Cooling > Rack-mounted air conditioner HR04A n > Running
Parameters and set Device name to Rack-mounted air conditioner HR04A_Device
name.
It is recommended that Supply air temperature settings in Running Parameters be set to 20° C,
Return air temperature settings be set to 30° C, and Dehumidification settings be set to 50% RH.
Log in to the ECC800 WebUI as an administrator.
Add an AIRSYS air conditioner.
Parameter
Name
Device attribute
Device Type
Connect To
Port
Device Address
Copyright © Huawei Technologies Co., Ltd.
Parameter
Value
Select Air Conditioner from the drop-down list
box.
Select Airsys from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the AIRSYS air
conditioner is connected to the COM1 port on the
ECC800. If the AIRSYS air conditioner is connected to
another port, enter the number of the connected port.
Enter the actual device address of the AIRSYS air
conditioner. In this section, 1 is used as an
example.
WARNING
Ensure that the device address of each AIRSYS air
conditioner is unique. Otherwise, the teamwork function
may be affected.