Procedure
Step 1 Set NetCol5000-C030 monitoring parameters.
1.
2.
3.
Step 2 Set the running parameters and control parameters for the NetCol5000-C030 on the WebUI.
1.
2.
3.
4.
After the smart cooling product is shut down, the temperature of the smart module increases
and data running is affected. Exercise caution when performing this operation.
----End

8.1.8.14 How to Set and Add a NetCol5000-C030 (over Modbus RTU)?

Prerequisites
One end of the straight-through cable has been connected to the J73 communications port on
the NetCol5000-C030 main control board, and the other end has been connected to the COM
port on the ETH converter.
Procedure
Step 1 Set NetCol5000-C030 monitoring parameters.
1.
2.
Issue 05 (2019-09-16)
Enter the NetCol5000-C030 home page, click Settings, choose user name admin and
enter password 000001. After login, the settings screen of the NetCol5000-C030 is
displayed.
Choose Settings > Comm Settings > IP Settings, set IP assigning mode to
Automatic(DHCP), and tap Submit.
Choose Settings > Comm Settings > Modbus Settings, and set Connection mode to
Server and client, Server encryption to Enable.
After setting parameters for the NetCol5000-C030, the ECC800 discovers the access from the smart
cooling product automatically.
The earlier version has Protocol setting on the screen. The actual screen prevails.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Cooling > NetCol5000-C0301.
0301 in NetCol5000-C0301 is variable and subject to change with the smart cooling product model and
connection sequence. The displayed value prevails.
On the Running Parameters tab page, set smart cooling product running parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).
Enter the NetCol5000-C030 home page, click Settings, choose the user name Admin
and enter password 000001. After login, the settings screen of the NetCol5000-C030 is
displayed.
Choose Settings > Comm Settings > Modbus Settings, choose Baud rate to 9600 and
set Comm address to 1.