Commissioning A Door Status Sensor (Connected To The Ai/Di Port On The Rack Environment Unit) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
6.
7.
8.
Step 2 Check the door status sensor functions.
Table 6-1 Commissioning the sensor
Check Method
Open the cabinet door.
----End
6.1.1.2 Commissioning a Door Status Sensor (Connected to the AI/DI Port
on the Rack Environment Unit)
If a door status sensor is installed, perform the following steps to configure it.
Context
Procedure
Step 1 Choose Monitoring > Cabinet > IT Cabinet1 > Cabinet Collector1 > Running
Parameters, set the door status sensor parameters.
Table 6-2 Parameter settings
Setting
area
AI/DI_1
Port
Settings
AI/DI_2
Port
Settings
Step 2 Check the door status sensor functions.
Table 6-3 Commissioning the sensor
Check Method
Issue 05 (2019-09-16)
Set Door1 sensor to Enable and click Submit.
Set Door1 sensor type to Door sensor, ensure that Door1 power supply is Yes, and
click Submit.
Perform the preceding operations to set parameters for ports AI/DI_2 to AI/DI_8.
If the sensor is prefabricated, only check its settings.
If multiple door status sensors are connected, commission one door status sensor first
and then commission the other door status sensors in the same way.
Object
Method
1. Choose AI/DI_1 sensor to Enable, click Submit.
Front door
status
2. Set AI/DI_1 sensor type to Door sensor, click Submit.
(AI/DI_1)
1. Choose AI/DI_2 sensor to Enable, click Submit.
Rear door
status
2. Set AI/DI_2 sensor type to Door sensor, click Submit.
(AI/DI_2)
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
Door1 DI alarm is generated on the active alarm page
of the app or WebUI.
Normal Connection Status
6 Feature Description
100