ECC800 Data Center Controller
User Manual

9.1 Linkage Control Introduction

The ECC800 provides the linkage control function. You can set logic rules and control the DO
output signal by collecting the signal value.
You can select signals (such as the AI/DI device status signals) and perform logic operations
such as AND, OR, NOT, GREATER THAN, LESS THAN, DELAY, and FILTER. The
operation result can be provided to the dry contact to meet the site control requirements.
Logic Parameters
The following are the inputs, operators, and outputs for linkage control logic programs:
Issue 05 (2019-09-16)
Inputs:
Sample: Such as AI/DI device signals.
Alarm: Such as AI/DI alarm signals.
Constant
Register: A register can combine multiple levels of logic programs.
Operators:
AND: The output is valid if both inputs are valid.
OR: The output is valid if either input is valid.
NOT: The output is the inverse value of the input signal or constant.
>: The output is active if the input is greater than the constant.
<: The output is active if the input is less than the constant.
DELAY: The output of the input signal or constant is delayed and the output is
constant.
FILTER: The output is active if the input reaches the constant.
Outputs:
Outputs are associated with dry contact outputs and can be used for generating
alarms or controlling devices.
Register: A register can combine multiple levels of logic programs.
Alarm: The operation result is generated as a new alarm.