ECC800 Data Center Controller
User Manual
Step 4 If there are multiple eLights, repeat
----End
Follow-up Procedure
To modify the parameters of a single eLight, do as follows:
1.
2.
Table 5-8 Function check
Item
Associated alarm
severity
NOTE
Issue 05 (2019-09-16)
The eLight actuator is automatically associated with the nearest access actuator in the smart module
view.
If there are one access actuator and two eLight actuators in an aisle, the access actuator is
automatically associated with the two eLight actuators.
Choose Monitoring > Aisle > eLight Actuator Group > eLight Actuator. The
Running Parameters page is displayed.
Select the Associated alarm severity as required and click Submit.
Alarm Severity
Selection
Critical
Critical, Major
Critical, Major, Minor
Critical, Major,
Minor, Warning
None
After you set the alarm severity, the eLight indicator is off if no alarm is generated.
Copyright © Huawei Technologies Co., Ltd.
Step 1–Step
3.
Description
If there is a critical alarm, the eLight
strip light turns on with a red light.
If there are multiple alarms, the eLight
strip light preferentially turns on with a
light corresponding to the high-severity
alarm. After the high-severity alarm is
cleared, the eLight strip light turns on
with a light corresponding to the
low-severity alarm.
NOTE
Critical: red light
Major: orange light
Minor: yellow light
Warning: white light
The eLight strip light is steady blue
(atmosphere light).
5 Power-On Commissioning