Networking Iboxs And Ibats In Wireless Mode - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Step 3 Click Unhide All Advanced Signals, set iBOX single battery qty., Batt. installation time,
Single battery capacity, Current source, and Battery string No.. Retain default values for
other parameters.
Table 6-24 Setting iBOX parameters
Parameter
iBOX/CIM single
battery qty.
Batt installation
time
Single battery
capacity
Current source
Battery string No.
----End

6.5.2 Networking iBOXs and iBATs in Wireless Mode

Prerequisites
Before networking, ensure that all the iBOXs and iBATs have no network parameters, that is,
the RF_Z indicator on the iBOX is steady green and the RUN/ALM indicator on the iBAT is
steady red.
Context
Issue 05 (2019-09-16)
Description
Total number of batteries monitored by
the iBOX/CIM
Actual time at which batteries are
installed
Single battery capacity refers to the
capacity of a single battery in a battery
string managed by the iBOX.
0–xxxA Hall
The actual specifications of the Hall
effect sensor prevail.
Set this parameter based on the planned
codes for iBOXs and battery strings.
The iBAT is connected to the iBOX in RF_Z networking mode.
If the RF_Z indicator on the iBOX is not steady on (green), press and hold down the networking
switch on the iBOX for 10–20 seconds to clear the original network.
If the RUN/ALM indicator on the iBAT is not steady red, hold down the iBAT networking switch for
at least 5 seconds to clear the original network.
If multiple iBOXs are connected, commission the iBOX one by one in the same way.
Otherwise, networking may be in disorder.
Indicator status:
Blinking at long intervals: The indicator is on for 1 second and then off for 1 second
alternately.
Blinking at super short intervals: The indicator is on for 0.05 seconds and then off
for 0.05 seconds alternately.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
Remarks
Set this parameter based
on the battery parameter
planned by the customer.
-
Obtain the battery capacity
from the battery label or
document.
-
Set this parameter based
on the customer's plan.
138