ECC800 Data Center Controller
User Manual
Figure 5-9 Adding alarm notification
Mailbox Address in Alarm Notification can be selected after it is added in Mailbox
Settings. Mobile Phone Number can be selected after it is added in SMS Settings.
Step 6 Click Confirm to access the re-authentication page. Enter Login password and click Submit.
----End
Follow-up Procedure
To modify or delete the email parameter settings, click Modify or Delete.

5.4 Commissioning the New Main Way

Context
In the new main way scenario, general input units and power distribution units communicate
with the ECC800 using the Modbus-MAC protocol. After the general input units and power
distribution units properly connect to the ECC800, the ECC800 automatically identifies the
units.
Then, you need to set parameters for the general input units and power distribution units;
otherwise, a false alarm may be generated.
Procedure
Step 1 Set parameters for general input units on the ECC800 WebUI.
1.
Issue 05 (2019-09-16)
Set parameters for general input unit 1.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
94