ECC800 Data Center Controller
User Manual
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings > Linkage Control.
Step 3 Ensure that Enable linkage control function is Yes.
Step 4 On the Linkage Group tab page, set Intelligent lighting to on.
Step 5 Check and configure the wireless networking (802.15.4) function of the AC actuator.
Before networking, ensure that both the ECC800 and AC actuator have no network
parameters. That is, the RF_Z indicators on the ECC800 and AC actuator are both steady
green.
1.
2.
3.
4.
Issue 05 (2019-09-16)
When using the intelligent lighting function, pay attention to the following:
If a foreign object is hung on the skylight ceiling of the smart module and when the foreign object
moves, the camera may mistakenly generate a motion detection alarm to change the lighting status.
When the human body moves, the camera generates a motion detection alarm and the lighting is
turned on. If the motion amplitude of the human body is small, the camera cannot generate the
motion detection alarm. If the lighting is turned off due to this reason, wave to the camera and the
lighting is turned on again.
If light greatly changes outside the smart module, the camera may mistakenly generate a motion
detection alarm and the lighting is mistakenly turned on.
If you manually turn off the lighting when you leave the smart module, the lighting may be turned
on again when the camera detects that the person leaves.
The effective detection distance of the multi-functional sensor is 2.5 m.
If the RF_Z indicator on the ECC800 is not steady green, hold down the SW button on
the ECC800 for more than 6 seconds to make the ECC800 enter non-networking status.
If the RF_Z indicator on the AC actuator is not steady green, hold down the BLINK
button on the AC actuator for more than 10 seconds to make the AC actuator enter
non-networking status.
Hold down the SW button on the ECC800 main control module for 2 seconds (1.2–5
seconds allowed). The RF_Z indicator on the ECC800 main control modules turns from
steady green to blinking green at super short intervals (blinking at 10 Hz, on for 0.05
seconds and then off for 0.05 seconds). The ECC800 enters the wireless networking
(802.15.4) pairing status.
Hold down the BLINK button on the AC actuator for 2 seconds (1–5 seconds allowed).
The RF_Z indicator on the AC actuator turns from steady green to blinking green
intermittently at super short intervals (blinking at super short intervals for 0.5 second and
then off for 0.5 second). The component enters the wireless network search status.
After the wireless networking (802.15.4) pairing succeeds, the RF_Z indicator on the AC
actuator starts to blink at long intervals.
After all AC actuators are networked, hold down the SW button on the ECC800 main
control module for 2 seconds (1.2–5 seconds allowed). The RF_Z indicator on the
ECC800 main control modules turns from blinking green at super short intervals to
blinking green at long intervals (blinking at 0.5 Hz, on for 1 second and then off for 1
second). The ECC800 exits the wireless networking (802.15.4) pairing status.
If two or more ECC800 controllers need to be networked in wireless (802.15.4) mode, only one system
can be networked at one time. During the networking, ensure that the RF_Z indicators on the ECC800
main control modules of other systems are blinking at long intervals or steady on.