ECC800 Data Center Controller
User Manual

8.1.8.12 How to Set and Add a NetCol5000-A042 Parameters?

Prerequisites
One end of the straight-through cable has been connected to the FE_1 port on the
NetCol5000-A042 main control board, and the other end has been connected to the POE port
on the ETH converter.
Procedure
Step 1 Set NetCol5000-A042 monitoring parameters.
1.
2.
3.
Step 2 Set the running parameters and control parameters for the 42 kW smart cooling product on the
ECC800 WebUI.
1.
2.
3.
4.
After the smart cooling product is shut down, the temperature of the smart module increases
and data running is affected. Exercise caution when performing this operation.
----End
8.1.8.13 How to Set and Add a NetCol5000-C030 Parameters (over Modbus
TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE port on the
NetCol5000-C030 main control board, and the other end has been connected to the POE port
on the ETH converter.
Issue 05 (2019-09-16)
Enter the NetCol5000-A042 home page, click Settings, choose the user name admin,
and enter password 000001. After login, the settings screen of the NetCol5000-A042 is
displayed.
Choose Comm Settings > IP Settings, set IP assigning mode to Automatic (DHCP),
and click Submit.
Choose Settings > Comm Settings > Modbus Settings, and set Connection mode to
Server and client, Server encryption to Enable.
After the NetCol5000-A042 parameters are set, the ECC800 can automatically identify the automatic
access of the NetCol5000-A042.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Cooling > NetCol5000-A0421.
0421 in NetCol5000-A0421 is variable and subject to change with the smart cooling product model and
connection sequence. The displayed value prevails.
On the Running Parameters tab page, set running parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).
Copyright © Huawei Technologies Co., Ltd.
8 FAQ
198