8.1.8.26 How to Set and Add the Multi-functional Sensor?

If a multi-functional sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the POE port on the
multi-functional sensor, and the other end has been connected to the POE port on the ETH
converter.
Procedure
Step 1 Set multi-functional sensor parameters.
On the WebUI, choose Monitoring > Aisle > Multi-Func Sensor Group > Multi-Func
Sensor1 > Running Parameters, ensure that Smoke enable and Temp enable are set to
Enable, set High temperature alarm threshold and other parameters as required, and then
click Submit.
Step 2 Check the functions of the multi-functional sensor.
Issue 05 (2019-09-16)
Parameter
Name
Communicatio
ns Port
Device
Address
Click Test Connect to check whether the independent deployment AI_DI unit connects
to the ECC800 properly.
a.
If the independent deployment AI_DI unit connects to the ECC800 properly, click
Confirm. The connected devices are displayed in the Number of connected
devices list.
b.
If the independent deployment AI_DI unit does not connect to the ECC800 properly,
check whether the cable between the independent deployment AI_DI unit and the
ECC800 is connected properly, whether the independent deployment AI_DI unit
and ECC800 are running properly, and whether the input parameters are consistent
with the parameters of the independent deployment AI_DI unit.
If multiple multi-functional sensors are connected, commission one multi-functional sensor first and
then commission the other multi-functional sensors in the same way.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the independent
deployment AI_DI unit is connected to the COM3 port on
the ECC800. If the independent deployment AI_DI unit is
connected to another port, set the COM port to the ECC800
port connected to the independent deployment AI_DI unit.
In this example, Device Address is set to 1. During
actual configuration, set the device address for the
independent deployment AI_DI unit based on the
actual situation.