ECC800 Data Center Controller
User Manual
Figure 8-8 Modifying basic configurations
Step 2 Click Modify Device and create a smart module plan view.
Step 3 Hold down the BLINK button on a device such as a smart ETH gateway for less than 1s to
report the blinking status to the ECC800. The corresponding device icon in the WebUI plan
view blinks. Check that the device positions and types in the plan view are consistent with the
actual situation by delivering the blinking command.
Issue 05 (2019-09-16)
If Room monitoring is set to No, draw a smart module view.
If Room monitoring is set to Yes, draw an equipment room view and smart module
view.
Drag the icons of registered devices (for example, the access actuator) and devices on the
cabinet list to appropriate positions in the layout, click a device icon, modify the value of
Device Name in the displayed Basic Configuration dialog box, and click Exit Edit
Mode to create a smart module plan view.
Click One-Click Layout. The power distribution devices, IT cabinets, and smart cooling
products on the cabinet list are automatically arranged in the view. The icons of other
registered devices (for example, the access actuator) and devices on the cabinet list need
to be manually arranged.
If the locations of devices automatically deployed are inconsistent with their actual locations, you can
manually adjust them.
There may be multiple same device icons on the editing page. If you are unable to determine the
positions of wireless communications devices such as the access actuator, general input unit, and power
distribution unit, use the following methods to identify them:
Hold down the BLINK button on a device for less than 1s to report the blinking status to the
ECC800. The corresponding device icon in the WebUI plan view blinks.
Drag a device in the WebUI plan view. The RUN indicator on the corresponding device blinks
intermittently at super short intervals.
If both room-level and smart module access actuators exist, modify the value of Device Name to
distinguish them.
The value of Device Name for the power distribution unit should be consistent with its label, for
example, NMW A 01.
If a room-level access control device and camera exist, drag them to the equipment room view.
You can click the camera icon in the view to display the camera web page.