ECC800 Data Center Controller
User Manual
Step 5 Check functions of the magnetic lock.
Table 6-11 Function commissioning
Check Method
When the aisle door is
normally closed, check
whether there is a door open
alarm on the ECC800.
----End
6.1.4 Commissioning an Emergency Door Release Button
Procedure
Step 1 Check the function of an emergency door release button.
Table 6-12 Function check
Check Method
When the room door is
properly closed,
short-circuit the wiring
terminals NC and COM or
NO and COM on the
emergency door release
button.
----End
6.2 Video Management
6.2.1 Preparing Documentation
Before commissioning a camera, prepare the following documents in addition to this
document.
Table 6-13 Documentation for Commissioning Preparation
Component
Issue 05 (2019-09-16)
Normal Connection
Status
There is no door open
alarm on the ECC800.
Normal Connection
Status
The room door is opened
properly.
Document
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
Troubleshooting
If a door open alarm is reported
when the door is closed,
relocate the magnetic lock and
magnet to minimize the
deviation until the door open
alarm is cleared.
Follow-up Procedure
Remove the short-circuit
cable from the wiring
terminals NC and COM or
NO and COM on the
emergency door release
button.
106