Step 5 Set water sensor parameters.
1.
2.
3.
Step 6 Check functions of water sensors.
Table 8-27 Function check
Check Method
Immerse the water
detection cable in
water.
----End

8.1.8.32 How to Set and Add the Electrode Water Sensor?

If a water sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the network cable has been stripped, core wires 6 and 7 have been connected to
the cable delivered with the electrode water sensor, and the other end of the network cable has
been connected to the AI/DI port on the rack environment unit.
Context
Procedure
Step 1 Set water sensor parameters.
Issue 05 (2019-09-16)
If the water sensor connects to the ECC800 properly, click Confirm. The connected
devices are displayed in the Number of connected devices list.
If the water sensor does not connect to the ECC800 properly, check whether the cable
between the water sensor and the ECC800 is connected properly, whether the water
sensor and ECC800 are running properly, and whether the input parameters are
consistent with the water sensor parameters.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > System > Water Sensor > Running Parameters.
Set the parameters based on actual conditions, and click Submit.
Normal Connection Status
Choose Monitoring > System >
Water Sensor > Running Info.
Check that Leakage status is Alarm
and Distance from the leakage
point is greater than 0 m.
Choose Home > Active Alarms.
Check that a water sensor alarm is
generated.
To use the AI/DI sensor, enable the corresponding AI/DI port and name the sensor. The
specific alarm then can be reported.
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is described.
Copyright © Huawei Technologies Co., Ltd.
8 FAQ
Alarm Clearance
Method
Wipe dry the water
detection cable. The alarm
disappears automatically.