8.1.8.24 How to Set and Add an IP Device?

Prerequisites
Context
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose Monitoring > System > ECC800 > Running Parameters.
Step 3 Click Unhide All Advanced Signals, on the IP Device Detection Parameters tab page, set
Online detection timeout interval to 29. The value range is 10 to 60 seconds. Click Submit.
Step 4 Set IP device num to 5. The value range is 0 to 100.
Step 5 Click Submit. The IP Device 1-5 tab page is displayed.
Step 6 On the IP Device 1-5 tab page, set Enable online detection IP device 1 to Enable.
Step 7 Click Submit.
Step 8 Specify IP device 1 address.
Step 9 Click Submit.
Step 10 (Optional) If you need to change the name of an IP device, perform the following steps:
1.
2.
3.
Issue 05 (2019-09-16)
An IP device is connected to the ECC800 over a switch. The device and ECC800 have
been powered on.
You have obtained the IP address of the IP device.
IP devices, such as ATMs, are devices with IP attributes in an equipment room or site. By
adding an IP device, you connect the device to the ECC800 in the same network so that
the ECC800 monitors the device status. If the IP device is offline, the ECC800 will
report a disconnection alarm on its WebUI.
Following is a procedure example about how to add five IP devices with the online
detection timeout interval being 29 seconds.
Online detection timeout interval is 30 by default, which means that the ECC800 determines that the
communication with the device is interrupted if the device has no response within 30 seconds.
Set IP device 1 address to the IP address of IP device 1. For example, set IP device 1 address to
192.168.2.137.
Add other IP devices in the same way.
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device Type to ECC800, set Device Name to ECC800, and click OK.
On the query result tab page, set the new signal name of IP device 1 to XXX and click
Submit.