Pin
Table 3-62 BCB_IN and BCB_OUT cascading port pin definitions
Pi
n
1
2
3
4
DIP Switch
Table 3-63 DIP switch description
No.
Issue 05 (2019-09-16)
Defini
Signal
tion
Description
ground
Defi
BCB_IN
nitio
Signal
n
Descripti
on
OL
Specifies
whether
the BCB
connects to
the signal
output
port.
STA
Signal
output port
for the
battery
circuit
breaker
status
DRV
Controls battery circuit
breaker trip and receives 12
V driving signals
GND
Secondary side ground
Definition
Copyright © Huawei Technologies Co., Ltd.
Status
Description
signal for
BCB
tripping.
BCB_OUT
Status
Signal
Description
Description
Specifies
Grounded:
whether the
BCB
cascaded BCBs
connected.
connect to the
Disconnected
signal input
: BCB not
port.
connected.
Monitors
Grounded:
whether the
The battery
cascaded BCBs
circuit
are connected
breaker is
to the input.
ON.
Disconnected
: The battery
circuit
breaker is
OFF.
0 V: There is
no driving
signal for
BCB
tripping.
12 V: There
is a driving
signal for
BCB
tripping.
3 Device Description
Initial
Remarks
Status
Initial
Status
Disconnec
ted
Disconnec
ted
0 V
Description
Descripti
on
Receives
BCB
commands
sent by the
UPS and
supports
BCB port
cascading
manageme
nt.