ECC800 Data Center Controller
User Manual
Table 6-4 Setting method
Cable Connection Scenario
The card reader with a keypad is
connected to WG_1 port on the access
actuator.
The card reader with a keypad is
connected to WG_2 port on the access
actuator.
Step 3 Check the functions of the access control device and access actuator.
Table 6-5 Function check
Check Method
Method 1: Attempt to open the door using
the configured authentication mode.
Method 2: On the WebUI, choose
Monitoring > Aisle > Access Actuator
Group > Access Actuator n, and click
Controls to open the door remotely.
Step 4 Check the functions of the cabinet electric lock.
Table 6-6 Function check
Check Method
Method 1: Ensure that the cabinet door is
closed, and attempt to open the door with an
IC card.
Method 2: On the WebUI, choose
Monitoring > Cabinet > IT Cabinet n >
E-LOCK n, and click Controls to open the
door remotely.
Issue 05 (2019-09-16)
Running Parameters, and set Logical level configuration for reader removed of the
corresponding card reader to High level alarm.
If the access control system uses a Card, Card and fingerprint, or Card, password
and fingerprint reader, retain the default value Low level alarm for Logical level
configuration for reader removed.
Copyright © Huawei Technologies Co., Ltd.
Setting Method
Set Logical level configuration for reader 1
removed to High level alarm. Logical level
configuration for reader 2 removed remains as
Low level alarm.
Set Logical level configuration for reader 2
removed to High level alarm. Logical level
configuration for reader 1 removed remains as
Low level alarm.
Normal Connection Status
For method 1: The aisle door is opened
successfully.
For method 2: After you choose Query >
Access Event on the WebUI, you can view
the type of this access control event.
Normal Connection Status
For method 1: Swipe an authorized IC card,
press the lower part of the cabinet electronic
lock when the green indicator blinks, and
open the cabinet electronic lock.
For method 2: After the cabinet electrical
lock is remotely opened, press the lower
part of the cabinet electronic lock after the
green indicator blinks, and open the cabinet
electronic lock. Choose Query > Access
Event on the WebUI, you can view the type
of this access control event.