6.8 VERIFICATION OF MEASUREMENT

6.8VERIFICATION OF MEASUREMENT
Set the relay as follows
GENERAL SETTINGS
NAME
PHASE CT RATIO
GROUND CT RATIO
STV GROUND CT RATIO
PHASE VT RATIO
PHASE VT CONNECTION
NOMINAL VOLTAGE
NOMINAL FREQUENCY
PHASE ROTATION
FREQUENCY REFERENCE
AUXILIARY VOLTAGE
NOTE:
ALL ANGLES INDICATED ARE LAGGING ANGLES
ALL VALUES OBTAINED IN THIS TEST MUST BE THE ONES CORRESPONDING TO THE PHASOR ONES
Apply the following voltage and frequency values to the relay:
CHANNEL
VI
VII
VIII
VX
Verify that the relay measures the values with an error of ±1 % of the applied value from 10V to 208V.
Apply the following current and frequency values to the relay:
CHANNEL
Ia (A)
Ib (A)
Ic (A)
IG (A)
ISG (A)
Verify that the relay measures the values with an error lower than ±0.5% of the test value or ± 10 mA, whichever is greater,
for phases and ground.
Verify that the relay measures the values with an error lower than ±1.5% of the test value or ± 1 mA, whichever is greater,
for sensitive ground (SG).
6
6-8
VALUE
UNITS
1.0
0.1
1.0
0.1
1.0
0.1
1.0
0.1
WYE
N/A
100 V
0.1
50 Hz
1 Hz
ABC
N/A
VI
N/A
VX
N/A
ANGLE
FREQUENCY
50 Hz
60 Hz
0
5
120º
0
5
240º
0
5
0
5
ANGLE
FREQUENCY
50 Hz
60 Hz
45º
0
15
165º
0
15
285º
0
15
0
15
0
5
F650 Digital Bay Controller
RANGE
1.0-6000.0
1.0-6000.0
1.0-6000.0
1.0-6000.0
WYE – DELTA
1-2250 V
50-60 Hz
ABC – ACB
VI-VII-VIII
VX – VN
50 Hz
60 Hz
50 Hz
60 Hz
50
100
150
200
50
100
150
200
50
100
150
200
50
100
150
200
50 Hz
60 Hz
50 Hz
60 Hz
10
5
1
0.1
10
5
1
0.1
10
5
1
0.1
10
5
1
0.1
1
0.1
0.01
0.005
6 COMMISSIONING

6.8.1 VOLTAGES

6.8.2 PHASE CURRENTS