Input of speed value above which the torque setpoint smoothing function selected in machine
data "Type current setpoint filter" (MD 1201) with the 2nd filter (low-pass/band-stop) is
activated. The user can apply this speed-dependent torque setpoint smoothing function to
reduce the speed ripple at high speeds (main spindle drives).
If 0 is entered as the threshold value, then the filter remains active as a low-pass filter over the
entire speed range. When other values are entered, two switchover speeds are calculated
from machine data MD 1245 (Threshold speed-dependent torque setpoint smoothing) and MD
1246 (Hysteresis speed-dependent torque setpoint smoothing).
n
upper
n
lower
Graphic representation:
Filter type
(2nd current setpoint filter)
Functionality: The switchover from "Feedthrough" to "Low-pass" takes place when the
absolute value of the actual speed exceeds the value n
from "Low-pass" to "Feedthrough" when the absolute value of the actual speed drops below
the value n
switchover speeds are identical.
1246
Input of hysteresis for the cut-in speed set in machine data "Threshold speed-dependent
torque setpoint smoothing" (MD 1245).
©
Siemens AG 1992 All Rights Reserved
SINUMERIK 840C (IA)
More user manuals on
Threshold speed-dependent torque setpoint smoothing
Default value
Lower input value
0.0
=
n
+
n
threshold
hysteresis
=
n
–
n
threshold
hysteresis
2nd filter
inactive
Speed n
n
+ n
threshold
hysteresis
n
threshold
n
- n
threshold
hysteresis
(In
I< n
). If the value 0 is entered for the hysteresis, then the two
lower
act
lower
Hysteresis speed-dependent torque setpoint smoothing
Default value
Lower input value
50.0
ManualsBase.com
7 Drive Machine Data (SIMODRIVE Drive MD)
Upper input value
0.0
50 000.0
Low-pass
2nd filter inactive
(In
upper
Upper input value
0.0
1 000.0
6FC5197- AA50
7.3.2 Drive MD (data description)
Active
at once
Units
rev/min
2nd filter
inactive
MD X246
MD X245
I n
) and vice versa
act
upper
Active
at once
Units
rev/min
t
7–113