F650 Digital Bay Controller
Appendix A:
LOGIC OPERANDS

A.1 Operands - F650 - model FX - GX

OPERANDS - F650 - MODEL FX - GX
Internal System Status
autocheck internal states (critical)
DSP Internal States (Critical to metering and
protection)
Flash Internal States (Critical to Relay configuration
and stored data)
IO Board States (Critical to operation and
protection)
IEC61850 INTERNAL STATES (NON CRITICAL)
GEK-113000-AF
DSP Communication Error: (0) Rignt communications
DSP COMM ERROR
between DSP and main processor; (1) Communication
Error between DSP and main processor
Magnetic Module Error: (0) Right Communication
MAGNETIC MODULE
between DSP and magnetic module processor; (1)
ERROR
Communication Error between DSP and magnetic
module processor
Calibration Error: (0) Right calibration values stored; (1)
CALIBRATION ERROR
The calibration values stored are out of the calibration
limits.
E2prom status :(0) Not configured or problems during
E2PROM STATUS
writing process ; (1) Configured and OK
Board F status: (0) Inactive - There is no communication
BOARD F STATUS
with the board (1) Active - There is communication with
the board.
Board G status: (0) Inactive - There is no communication
BOARD G STATUS
with the board (1) Active - There is communication with
the board.
Board H status: (0) Inactive - There is no communication
BOARD H STATUS
with the board (1) Active - There is communication with
the board.
Board J status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
BOARD J STATUS
the board.
F650 DIGITAL BAY CONTROLLER
A-1