ABB RELION REX640 Technical Manual page 606

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
600
GUID-5D9C2435-8318-461B-81C7-870C60358E9A V1 EN
Figure 331:
The limits and operation of the fifth harmonic blocking when both
blocking and deblocking features are enabled using the Harmonic
deblock 5.H control parameter.
The fifth harmonic blocking has a hysteresis to avoid rapid fluctuation between
"TRUE" and "FALSE". The blocking also has a counter, which counts the required
consecutive fulfillments of the condition. When the condition is not fulfilled, the
counter is decreased (if >0).
Also the fifth harmonic deblocking has a hysteresis and a counter which counts the
required consecutive fulfillments of the condition. When the condition is not fulfilled,
the counter is decreased (if >0).
Waveform blocking
The biased low stage can always be blocked with waveform blocking. The stage can
not be disabled with the Restraint mode parameter. This algorithm has two parts. The
first part is intended for external faults while the second is intended for inrush
situations. The algorithm has criteria for a low current period during inrush where also
the differential current (not derivative) is checked.
Biased low stage
The current differential protection needs to be biased because the possible appearance
of a differential current can be due to something else than an actual fault in the
transformer (or generator).
In the case of transformer protection, a false differential current can be caused by:
CT errors
Varying tap changer positions (if not automatically compensated)
Transformer no-load current
Transformer inrush currents
Transformer overexcitation in overvoltage
Underfrequency situations
CT saturation at high currents passing through the transformer
1MRS759142 C
REX640
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents