Figure 180:
Functionality of numerical multiple-stage overcurrent protection
The coordination plan is an effective tool to study the operation of time selective
operation characteristics. All the points mentioned earlier, required to define the
overcurrent protection parameters, can be expressed simultaneously in a coordination
plan. In
Figure
181, the coordination plan shows an example of operation
characteristics in the LV-side incoming feeder and radial outgoing feeder.
Section 4
Protection functions
319