1MRS759142 C
Table 609:
LREFPNDF Group settings (Advanced)
Parameter
Values (Range)
Minimum operate time
Restraint mode
Start value 2.H
Table 610:
LREFPNDF Non group settings (Basic)
Parameter
Values (Range)
Operation
CT connection type
Table 611:
LREFPNDF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
4.3.4.9
REX640
Technical Manual
Unit
40...300000
ms
1=None
2=Harmonic2
10...50
%
Unit
1=on
5=off
1=Type 1
2=Type 2
Unit
0...60000
ms

Monitored data

Table 612:
LREFPNDF Monitored data
Name
START_DUR
RES2H
ID_COSPHI
IB
LREFPNDF
Step
Default
1
40
1=None
1
50
Step
Default
1=on
2=Type 2
Step
Default
1
20
Type
Values (Range)
FLOAT32
0.00...100.00
BOOLEAN
0=False
1=True
FLOAT32
0.00...80.00
FLOAT32
0.00...80.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 4
Protection functions
Description
Minimum operate time
Restraint mode
The ratio of the 2. harmonic to
fundamental component required for
blocking
Description
Operation Off / On
CT connection type
Description
Reset delay time
Unit
Description
%
Ratio of start time /
operate time
2nd harmonic restraint
xIn
Directional differential
current Id cosphi
xIn
Bias current
Status
671