Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.4.5.9
Table 698:
MNSPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
Operating curve type
Machine time Mult
Operate delay time
Table 699:
MNSPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
Maximum operate time
Minimum operate time
Cooling time
Table 700:
MNSPTOC Non group settings (Advanced)
Parameter
Values (Range)
Current reference
Reset delay time
REX640
Technical Manual
Table 697:
MNSPTOC Output signals
Name
OPERATE
START
BLK_RESTART

Settings

Unit
0.01...0.50
xIn
5=ANSI Def. Time
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
5.0...100.0
100...120000
ms
Unit
1=on
5=off
500000...7200000
ms
100...120000
ms
5...7200
s
Unit
0.30...2.00
xIn
0...60000
ms
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
BOOLEAN
Overheated machine reconnection blocking
Step
Default
0.01
0.20
15=IEC Def. Time
0.1
5.0
10
1000
Step
Default
1=on
1000
1000000
1
100
1
50
Step
Default
0.01
1.00
1
20
Section 4
Protection functions
Description
Start value
Selection of time delay curve type
Machine related time constant
Operate delay time
Description
Operation Off / On
Max operate time regardless of the
inverse characteristic
Minimum operate time for IDMT curves
Time required to cool the machine
Description
Rated current (Ir) of the machine (used
only in the IDMT)
Reset delay time
765

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents