Signals; Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.1.5.7
4.1.5.8
Table 411:
T2PTTR Group settings (Basic)
Parameter
Values (Range)
Env temperature Set
Temperature rise
Max temperature
Table continues on next page
REX640
Technical Manual
Single time constant
(min)
50
55
60
65
70
75
The default Max temperature setting is 105°C. This value is chosen since even though
the IEC 60076-7 standard recommends 98°C as the maximum allowable temperature
in long-time loading, the standard also states that a transformer can withstand the
emergency loading for weeks or even months, which may produce the winding
temperature of 140°C. Therefore, 105°C is a safe maximum temperature value for a
transformer if the Max temperature setting value is not given by the transformer
manufacturer.

Signals

Table 409:
T2PTTR Input signals
Name
I3P
BLOCK
AMB_TEMP
Table 410:
T2PTTR Output signals
Name
OPERATE
START
ALARM
BLK_CLOSE

Settings

Unit
-50...100
°C
0.0...200.0
°C
22.0...200.0
°C
Short time constant (min) Long time constant (min) Weighting factor p
5.1
82
5.6
90
6.1
98
6.7
107
7.2
115
7.8
124
Type
Default
Description
SIGNAL
-
Three-phase currents
BOOLEAN
0=False
Block signal for activating the blocking mode
FLOAT32
0
The ambient temperature used in the calculation
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
BOOLEAN
Thermal Alarm
BOOLEAN
Thermal overload indicator. To inhibite reclose.
Step
Default
1
40
0.1
78.0
0.1
105.0
Section 4
Protection functions
0.4
0.4
0.4
0.4
0.4
0.4
Description
Ambient temperature used when no
external temperature measurement
available
End temperature rise above ambient
Maximum temperature allowed for the
transformer
373