1MRS759142 C
3.20.16.6
REX640
Technical Manual
Outputs WARNING and URES_WARNING indicate questionable quality data of
system measurements for selected U3P and URES, respectively.
Depending on the connected U3P channels to the voltage switch, the
Primary voltage settings between the source U3P must match.
Respectively, depending on the connected URES channels, the
Primary voltage settings between the source URES must match.
Setting validation for the primary voltages fails unless they are all
stored simultaneously to the protection relay.

Signals

Table 238:
VMSWI Input signals
Name
Type
U3P1
SIGNAL
U3P2
SIGNAL
U3P3
SIGNAL
U3P4
SIGNAL
URES1
SIGNAL
URES2
SIGNAL
URES3
SIGNAL
URES4
SIGNAL
SWITCH_TO2
BOOLEAN
SWITCH_TO3
BOOLEAN
SWITCH_TO4
BOOLEAN
Table 239:
VMSWI Output signals
Name
Type
SOURCE1
BOOLEAN
SOURCE2
BOOLEAN
SOURCE3
BOOLEAN
SOURCE4
BOOLEAN
U3P
SIGNAL
URES
SIGNAL
ALARM
BOOLEAN
WARNING
BOOLEAN
Default
Description
-
Three-phase voltages 1
-
Three-phase voltages 2
-
Three-phase voltages 3
-
Three-phase voltages 4
-
Residual voltage 1
-
Residual voltage 2
-
Residual voltage 3
-
Residual voltage 4
0=False
Switch to source 2
0=False
Switch to source 3
0=False
Switch to source 4
Description
Selected voltage source is source 1
Selected voltage source is source 2
Selected voltage source is source 3
Selected voltage source is source 4
Three-phase voltages
Residual voltage
Alarm
Warning