Figure 437:
An example of a delayed reset in the inverse time characteristics.
When the start becomes active during the reset period, the operate
time counter continues from the level corresponding to the drop-off
(reset time = 0.50 · Cooling time)
Overexcitation IDMT curves 1, 2 and 3
The base equation for the IDMT curves "OvExt IDMT Crv1", "OvExt IDMT Crv2"
and "OvExt IDMT Crv3" is:
ak b
100
M
+ −
c
t s
e
( ) =
60
GUID-368D8558-6F96-4C4C-80D8-063EFF6DF122 V1 EN
t(s) Operate time in seconds
M
Excitation level (U/f ratio or volts/hertz) in pu
Time multiplier setting
k
The constant "60" in
Table 767:
Parameters a, b and c for different IDMT curves
Operating curve type
a
setting
OvExt IDMT Crv1
2.5
OvExt IDMT Crv2
2.5
OvExt IDMT Crv3
2.5
Protection functions
Equation
converts time from minutes to seconds.
b
115.00
113.50
108.75
Section 4
(Equation 203)
c
4.886
3.040
2.443